100
english
Error
Cause
class
Sensor voltage supply
faulty
Actuator voltage supply
faulty
Internal intermediate
voltage faulty
Internal device
internal
error
Initialization failed
PROFIsafe
Wrong destination
external
configuration
address set
Trigger
Effect
Remedy
Check sensor/actuator
voltage supply (US/UA).
Restart or replace.
device.
Check sensor/actuator voltage
supply (US/UA). Restart device
and replace if needed.
Restart device and replace if
needed.
Check PROFIsafe
configuration (F-Dest_Add)
and reload. Acknowledge
device on controller side or
reconfigure on device (F_Dest_
Add). Restart device and
replace if needed.