Diagnostics
Error code
Error
class
Display PROFINET
69
0x004B
external
70
71
72
73
internal
75
76
77
78
internal
79
80
external
www.balluff.com
Cause
Trigger
Configuration
F_iPAR_CRC
error
comparison faulty
Software procedure
error
Input test pulse faulty
Internal device
PROFIsafe driver
error
defective
CPU data exchange
error
Internal device
Memory error
error
Input wiring
Input delay too short
(sensors)
Effect
Remedy
Check system compatibility
(see Section 2.8) and correct if
needed, reload configuration,
recalculate iPar_CRC in P-Tool
and send to controller.
Acknowledge device on
controller side.
Check ground connection.
Restart device and replace if
needed.
Check input port configuration
(increase input delay if
necessary). Acknowledge
device on controller side.