DOSING PUMP INSTALLATION ON THE ALREADY
INSTALLED BYPASS VALVE
Display and
keypad
Mineral solution container
/
Insert the heads of the four M6×25 hexagon socket head screws through the bayonet holes on the de-
vice-side flange "G" (G=Gerät [device]) of the built-in rotary flange (see fig. 6).
/
Turn the dosing pump clockwise until it reaches the stop.
/
Tighten the four M6×25 hexagon socket head screws.
Select the tightening torque (about 4 Nm) so that the seal is effective and the dos-
ing pump is not damaged or strained!
The profile of the profiled flange gasket must point towards the bypass valve. If this is not observed, water
leaks may occur resulting in water damage to the home and furnishings and equipment.
/
Unscrew the lid of the mineral solution container.
/
Remove the seal with a sharp knife.
/
Push the mineral solution container on from below over the suction lance and screw home on the pump
housing.
Dosing pump
Fig. 7: Dosing pump with bypass valve
Built-in rotary flange
Bypass valve
Power supply unit
53