UK | 9 Mounting
9.8 Mounting and teaching in the radio
components (EnOcean)
When radio mode is activated, En-
i
Ocean radio components, such as
master or slave units or sensors, can
be taught-in directly on ventilation
units. For range of radio components
 Technical data.
The PP 45 EO EnOcean module can
i
only be taught in with the commission-
ing software (RLS 45 K). This activates
teach-in mode and sends a radio tele-
gram. All radio sensors/radio switches
are taught in directly on the PP 45 EO.
Only the EnOcean module is taught in
on the master.
Purely radio-
PP 45 combi system with
controlled
wired and radio-controlled
PP45 system
components
DS 45 RC
+
PP 45 RC
PP 45 RC
...
Purely radio-controlled PP 45 system
DS 45 RC
1. Simply glue
location on the wall. Alternatively, the radio
switch can also be screwed onto the wall
(mounting material provided by customer).
2. Use the "Learn button" to activate teach-
ing-in mode on the ventilation unit. For
more information about teaching-in
 Operating instructions, Chapter 7.
3. For basic unit settings, such as "Block Off
function".
72
RLS 45 K
PP 45 EO
+
+
max. 6
PP 45 RC
PP 45 K
PP 45 O
to installation
PP 45 combi system with
PP 45 EO extension module can only
i
be combined with PP 45 RC unit pairs.
Wired operation is needed for other
unit types.
1. Install EnOcean extension module
. For more information  Acces-
PP 45 EO
sories instructions. If necessary, include
a separate distribution box in the wiring
planning.
2. Connect EnOcean extension module to
RLS 45 K
control (RS485)  Wiring dia-
grams in the appendix.
3. Start up ventilation system, activate in
EnOcean service mode  Chap. 14.
Installing humidity sensor
In wired systems, the integrated humidity sen-
sor is inserted into the
room air control.
PP 45 RC
In
radio-controlled units, the inte-
grated humidity sensor is installed directly in
the ventilation unit.
For installation and wiring of an external sen-
sor  Wiring diagrams in the appendix.
Installing humidity sensor in
RLS 45 K
1. Install room air control as described be-
fore.
NOTICE
Unit damage/no function if the humidity
sensor is installed incorrectly. Do not bend
pins. Insert sensor up to stop in bush.
2. Insert humidity sensor
interface Arrow.
PP 45 EO
PP 45 HYI
RLS 45 O
RLS 45 K
or
RLS 45 O
or
PP 45 HYI
at I2C