DANGER
Failure to observe the relevant reg-
ulations result in a risk for electrical
installations.
Be sure to observe the relevant regu-
lations for electrical installation; e.g. EN
50110-1, in Germany this is particularly
VDE 0100, with the corresponding parts.
A mains isolation device with contact
openings of at least 3 mm at each pole is
mandatory.
Only connect units to a permanently
wired electrical installation.
The units may only be operated using
the voltage and frequency shown on the
rating plate.
230 V AC: RLS 45 O, RLS 45 K and
PP 45 RC
12 V DC: PP 45 O and PP 45 K
!
DANGER
Risks from parts which may affect the
ventilation system which are added or
modified at a later date.
Parts (range hood, air-ventilated fireplace
etc.) which are added or modified at a later
date may result in health risks and operation
which is not permitted.
Parts may only be added or modified at a
later date if system compatibility is estab-
lished/ensured by a planning office. If using
an exhaust air range hood or air-ventilated
fireplace, this must be accepted by a profes-
sional chimney sweep.
!
DANGER
Danger if operating a ventilation unit not
mounted in full. If the unit is open and is
being operated without a filter, a running fan
can be touched. Risk of electric shock from
components of the PP 45 RC unit without
electrical protection.
Only operate the ventilation units when
completely installed.
Wait until the fan is stationary.
3 Safety instructions | UK
!
DANGER
Risk of injury and health risk when using
accessory elements which have not been
approved. The ventilation unit is tested and
approved with original accessory elements
(e.g. air filters).
The unit may only be operated with origi-
nal components.
Modifications and alterations to units are
not permitted and release the manufacturer
from any guarantee obligations and liability.
!
DANGER
Risk of death from carbon monoxide
when operating with air-ventilated fire-
places.
Ensure sufficient supply air intake during
operation with air-ventilated fireplaces. Note
maximum permissible pressure difference
per housing unit. The consent of a profes-
sional chimney sweep is needed in all cases.
Ventilation units may only be installed
in rooms, apartments or residential units of
a comparable size, in which air-ventilated
fireplaces are installed if:
● a parallel operation of air-ventilated fire-
places for liquid or gaseous fuels and the
air-extracting equipment can be prevented
via safety devices, or
● the extraction of exhaust gas from the
air-ventilated fireplaces is monitored by
special safety equipment. In the case of
air-ventilated fireplaces for liquid or gas-
eous fuels, the fireplace or the ventilation
system must be switched off if the safety
device is triggered.
In the case of air-ventilated fireplaces for
solid fuels, the ventilation system must
be switched off if the safety device is
triggered.
59