DANGER
Failure to observe the relevant reg-
ulations result in a risk for electrical
installations.
 Be sure to observe the relevant regu-
lations for electrical installation; e.g. EN
50110-1, in Germany this is particularly
VDE 0100, with the corresponding parts.
 A mains isolation device with contact
openings of at least 3 mm at each pole is
mandatory.
 Only connect units to a permanently
wired electrical installation.
 The units may only be operated using
the voltage and frequency shown on the
rating plate.
230 V AC: RLS 45 O, RLS 45 K and
PP 45 RC
12 V DC: PP 45 O and PP 45 K
!
DANGER
Risks from parts which may affect the
ventilation system which are added or
modified at a later date.
Parts (range hood, air-ventilated fireplace
etc.) which are added or modified at a later
date may result in health risks and operation
which is not permitted.
 Parts may only be added or modified at a
later date if system compatibility is estab-
lished/ensured by a planning office. If using
an exhaust air range hood or air-ventilated
fireplace, this must be accepted by a profes-
sional chimney sweep.
!
DANGER
Danger if operating a ventilation unit not
mounted in full. If the unit is open and is
being operated without a filter, a running fan
can be touched. Risk of electric shock from
components of the PP 45 RC unit without
electrical protection.
 Only operate the ventilation units when
completely installed.
 Wait until the fan is stationary.
3 Safety instructions | UK
!
DANGER
Risk of injury and health risk when using
accessory elements which have not been
approved. The ventilation unit is tested and
approved with original accessory elements
(e.g. air filters).
 The unit may only be operated with origi-
nal components.
 Modifications and alterations to units are
not permitted and release the manufacturer
from any guarantee obligations and liability.
!
DANGER
Risk of death from carbon monoxide
when operating with air-ventilated fire-
places.
Ensure sufficient supply air intake during
operation with air-ventilated fireplaces. Note
maximum permissible pressure difference
per housing unit. The consent of a profes-
sional chimney sweep is needed in all cases.
Ventilation units may only be installed
in rooms, apartments or residential units of
a comparable size, in which air-ventilated
fireplaces are installed if:
● a parallel operation of air-ventilated fire-
places for liquid or gaseous fuels and the
air-extracting equipment can be prevented
via safety devices, or
● the extraction of exhaust gas from the
air-ventilated fireplaces is monitored by
special safety equipment. In the case of
air-ventilated fireplaces for liquid or gas-
eous fuels, the fireplace or the ventilation
system must be switched off if the safety
device is triggered.
In the case of air-ventilated fireplaces for
solid fuels, the ventilation system must
be switched off if the safety device is
triggered.