Herunterladen Inhalt Inhalt Diese Seite drucken

Mounting; During The Shell Phase - Maico PP 45 K Installationsanleitung

Vorschau ausblenden Andere Handbücher für PP 45 K:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

UK | 9 Mounting

9 Mounting

9.1 During the shell phase

Installing wall sleeve(s)
A Outline of internal cover
B Cable feedthrough, position depends
on unit type
NOTICE
Installation position, internal wall: Once
the plaster has been applied or wallpaper put
up etc., the wall sleeve must end flush with
the internal wall.
Installation position, external wall: Once
the external plaster has been applied, wall
sleeve must protrude 10 to 15 mm beyond
it – projection is needed as drip edge inside
the external cover.
66
The following steps should be taken for all
wall sleeves and external covers
1. Determine installation location(s). Observe
installation dimensions and minimum
spacing to the wall and ceiling. Fit empty
ducting/cable feedthrough.
! WARNING
Risk of injury if a wall sleeve or external/
internal cover come loose.
Only mount on walls with sufficient load-bear-
ing capacity. The wall sleeve must be firmly
plastered in.
NOTICE
Unit damage and damage to brickwork
resulting from condensate caused by
incorrect installation. Condensate will run
towards the inside wall if the core hole is
drilled at too slight of an incline. Mount the
wall sleeve with an incline of 1...2 % to the
external wall so that any condensation which
collects can drain outwards. Ensure that the
wall sleeve protrudes 10 to 15 mm beyond
the external wall.
2. Drill core hole. Observe inclines of 1 to 2
% towards the external wall.
Recommendation: Drill
i
align the
160 wall sleeve with poly-
Ø
styrene shims to an incline of 1 to 2 %.
3. Shorten wall sleeve to wall thickness
+ 10...15 mm (internal/external wall fully
plastered).
4. Deburr wall sleeve on both sides.
5. Place wall sleeve in core hole such that it
protrudes 10...15 mm beyond the external
wall.
6. Close off wall sleeve on both sides with
plaster protective covers provided.
7. For a
162 core hole, fix the wall sleeve
Ø
with construction adhesive in the core
hole.
8. For a
182 core hole, align wall sleeve
Ø
and fix on inside and outside with shims
provided.
182 and
Ø

Quicklinks ausblenden: