IDPlus 961-974 -HC
WIRING GUIDELINES
LOOSE WIRING CAN RESULT IN ELECTRIC SHOCK AND FIRE
Tighten the connections in compliance with the technical specifications for the torque values.
Failure to follow these instructions will result in death or serious injury.
Use copper conductors (obligatory).
The table below shows the type and size of cables to use for screw terminals with spacing 5.08 mm (0.2 in.):
6.5
mm
0.26
in.
mm
2
0.2...2.5
AWG
24...14
Ø 3.5 mm (0.14 in.)
UNINTENDED EQUIPMENT OPERATION
The signal cables (probes, digital inputs, communication and relative power supplies) of the device must be
laid separately from the power cables.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
9IS54671.00 10 - 2018
0.2...2.5
0.25...2.5
0.25...2.5
24...14
24...14
24...14
0.5...0.6
N•m
C
lb-in
4.42...5.31
WARNING
DANGER
2 x 0.2...0.75
2 x 0.2...0.75 2 x 0.25...0.75
2 x 24...18
2 x 24...18
www.eliwell.com
2 x 0.5...1.5
2 x 20...16
2 x 24...18
6/40