IDPlus 961-974 -HC
PAR. Description
Alarm indicating end of defrost as a result of timeout.
dAt
n (0) = no; y (1) = yes.
An external alarm locks the regulators.
rLO
n (0) = does not lock; y (1) = locks.
SA3 Probe 3 alarm set point.
dA3 Probe 3 alarm differential.
LIGHTS & DIGITAL INPUTS (folder "Lit")
Digital input for switching off utilities.
0 = disabled; 1 = disables the fans;
dOd
2 = disables the compressor;
3 = disables fans and compressor.
dAd Activation delay for digital input.
dCO Delay in deactivating compressor after door opened.
AUX relay associated to door switch.
AuP
n (0) = not associated; y (1) = associated.
PRESSURE SWITCH (folder "PrE")
Number of errors allowed per maximum/minimum pressure
PEn
switch input.
PEi Minimum/maximum pressure switch error count interval.
PEt Delay in deactivating compressor after door opened.
COMMUNICATION (folder "Add")
Selection of communication protocol.
PtS
T (0) = Televis; d (1) = Modbus.
9IS54671.00 10 - 2018
Range
UM
AP1 AP2 AP3 AP4
n/y
flag
n
n/y
flag
n
-58.0...302 °C/°F 0.0
1.0...50.0 °C/°F 1.0
0...3
num
0
0...255
min
0
0...255
min
1
n/y
flag
n
0...15
num
0
1...99
min
1
0...255
min
0
t/d
flag
t
www.eliwell.com
n
n
n
n
n
n
0.0
0.0
0.0
1.0
1.0
1.0
0
0
0
0
0
0
1
1
1
n
y
n
0
0
0
1
1
1
0
0
0
t
t
t
34/40