IDPlus 961-974 - HC

FURTHER INFORMATION

Mechanical Characteristics
Dimensions:
Mounting panel thickness:
Terminals:
Connectors:
Input Characteristics
Display range:
Accuracy:
Resolution:
Buzzer:
Analogue Inputs:
Digital Inputs:
NOTE: Contact our sales office for the relay and power supply ratings
NOTE: The technical specifications stated in this document regarding the measurement (range, accuracy,
resolution, etc.) refer strictly to the instrument and not to any accessories provided, such as the probes.
9IS54671.00 10 - 2018
Frontal 78.6x37 mm (3.09x1.46 in.), depth 59 mm (2.32 in.) (excluding terminals)
0.5...10.0 mm (0.02...0.39 in.)
screw-type
TTL serial for connection of CopyCard, UNICARD or DI2 (IDPlus 974 -HC only)
ntc: -50...110°C (-58...230°F); Ptc: -55...140°C (-67...284°F);
Pt1000: -55.0...150°C (-67°F...302°F); (on 3-digit display with +/- sign)
ntc/Ptc/Pt1000: -55...70°C (-67...158°F): Better than 0.5% of integral-scale +1 digit.
Pt1000: 70...150°C (158...302°F): Better than 0.6% of integral-scale +1 digit.
0.1°C (0.1°F)
YES (depends on model)
IDPlus 961 -HC: 1* ntc/Ptc/Pt1000 input
IDPlus 974 -HC: 2* ntc/Ptc/Pt1000 inputs
IDPlus 961 -HC: 1 voltage free digital input (DI1*)
IDPlus 974 -HC: 2 voltage free digital inputs (DI1* and DI2**)
(*) DI1 can also be configured as a probe input (H11=0 and H43=y)
(**) DI2, if activated, should be connected to terminals 1-2 of the TTL connector
(IDPlus 974 -HC)
www.eliwell.com