IDPlus 961-974 -HC
PAR. Description
Select the unit of measure used when displaying the
temperature recorded by the probes. 0 = °C, 1 = °F.
dro
NOTE: switching between °C and °F DOES NOT modify the
SEt, diF values, etc. (e.g. set=10°C becomes 10°F).
Selects the type of value to show in the display.
0 = Setpoint;
ddd
1 = probe Pb1;
2 = probe Pb2;
3 = probe Pb3.
HACCP (folder "HCP")
SHH Maximum HACCP alarm signals threshold.
SLH Minimum HACCP alarm signals threshold.
Minimum dwelling time in critical area for the event to be recorded.
drA
After this time a HACCP alarm will be logged and signaled.
drH HACCP alarm reset time from last reset.
Enable HACCP and alarm relay functions.
0 = HACCP alarms NOT enabled;
H50
1 = HACCP alarms enabled and alarm relay NOT enabled;
2 = HACCP alarms enabled and alarm relay enabled.
H51 HACCP alarm override time.
CONFIGURATION (folder "CnF"): Switched off and on again the device each time the configuration
H00 Probe type selection. 0 = Ptc; 1 = ntc; 2 = Pt1000.
9IS54671.00 10 - 2018
of the parameters is changed
Range
UM
AP1 AP2 AP3 AP4
0/1
flag
0
0...3
num
1
-55.0...150 °C/°F 0.0
-55.0...150 °C/°F 0.0
0...99
min
0
0...250
hours
0
0/1/2
num
0
0...250
min
0
0/1/2
num
1
www.eliwell.com
0
0
0
1
1
1
10.0
0.0
0.0
-10.0
0.0
0.0
10
0
0
24
0
0
1
0
0
0
0
0
1
1
1
36/40