Eliwell EWPlus 902 Handbuch Seite 32

Elektronische regler für kühleinheiten
Inhaltsverzeichnis

Werbung

IDPlus 961-974 -HC
PAR. Description
tdC "Blast Chilling" duration.
dCC Defrost activation delay after a "Blast Chilling Cycle".
DEFROST (folder "dEF")
Type of defrost.
0 = electric defrost;
dty
1 = reverse cycle defrost;
2 = defrost independent of compressor.
dit Interval between the start of two consecutive defrost cycles.
Selects the count mode for the defrost interval.
0 = compressor running time;
dCt
1 = device running time;
2 = Every time the compressor stops, a defrost cycle is carried
out.
dOH Delay preceding start of first defrost after call.
dEt Defrost time-out; determines the maximum defrost duration.
dSt Defrost end temperature - determined by probe Pb2.
Determines whether or not the instrument must defrost at
dPO
power-up. n (0) = no; y (1) = yes.
FANS (folder "FAn")
FSt Fans disabling temperature.
FAd Fan activation differential.
Fdt Fan activation delay after a defrost cycle.
dt Dripping time.
9IS54671.00 10 - 2018
Range
UM
AP1 AP2 AP3 AP4
0...255
min
0
0...255
min
0
0/1/2
num
0
0...250
hours
6
0/1/2
num
1
0...59
min
0
1...250
min
30
-50.0...150 °C/°F 8.0
n/y
flag
n
-58.0...302 °C/°F 50.0 50.0 50.0 50.0
1.0...50.0 °C/°F 2.0
0...250
min
0
0...250
min
0
www.eliwell.com
0
0
0
0
0
0
0
0
1
6
6
6
1
1
1
0
0
0
30
30
30
8.0
8.0
8.0
n
n
n
2.0
2.0
2.0
0
0
0
0
0
0
32/40

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ewplus 961Ewplus 971Ewplus 974

Inhaltsverzeichnis