LOADING DEFAULT APPLICATIONS
The procedure for loading one of the default applications is:
• when the device is powered up, hold down
• browse the various applications (AP1...AP4) using the
• select the desired application using the
wait for the timeout;
• if the operation is successful, the display will show "y", if not, it will show "n";
• after a few seconds the instrument will return to the main display.
Loading one of the pre-set Applications will restore the original factory settings.
UNINTENDED EQUIPMENT OPERATION
Verify all the relevant parameters after uploading a default application.
Failure to follow these instructions can result in equipment damage.
DEFAULT PARAMETER SETTINGS
The devices can be used to set the parameters to the default values, by loading one of the pre-set applications
AP1...AP4 (see paragraph "LOADING DEFAULT APPLICATIONS").
SETPOINT EDIT LOCK
The keypad can be locked by entering the "Basic Commands" menu using the
within 2 seconds or through suitable programming of the "LOC" parameter (see "diS" folder).
With the keypad locked the Setpoint is read-only.