Node-ID: ddd
New Node-ID: ddd
After pressing ENTER again the new node number is entered. If the configuration is successful, (+) is
indicated in the first line and the CAN analyser immediately performs a node reset. Thus the new
number becomes valid immediately.
If the configuration is not successful, (-) is shown in the first line.

Menu Set Baudrate

After selection of the menu point first enter the number of the node (3 digits, decimal) for which the
new setting is to be valid.
Node-ID: ddd
After pressing ENTER the new baud rate can be directly entered as a decimal numerical value (4
digits, decimal, e.g. 50, 250, 1000) in the next line. The default value is 125 (125 Kbits/s).
Node-ID: ddd
Baudrate: dddd
After pressing ENTER again the new baud rate is entered. If the configuration is successful, (+) is
indicated in the first line. The baud rate does not become valid until the user has performed a
node reset (via software or by turning power on and off).
If the configuration is not successful, (-) is shown in the first line.