Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 32

6 Parameter Table

6
Parameter Table
This parameter table shows the most
important parameters. Default settings
are bold type. Refer to the instruction
manual for a complete list of parameters.
Par.
Name
Initialization Parameters
Selects which parameters are
accessible via the digital opera-
Access
tor.
A1-01
Level
0:Operation only
Selection
1:User Parameters
2:Advanced Access Level
Selects the Control Method of
the drive.
Control
0: V/f Control
A1-02
Method
2: Open Loop Vector (OLV)
Selection
5: PM Open Loop Vector (PM)
Note: Not initialized with A1-03!
Resets
default. (returns to 0 after initial-
ization)
No Initialize
Initialize
1110: User Initialize (The user
A1-03
Parame-
must first set user parameter
ters
values and then store them
using parameter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
Operation Mode Selection
0:Operator - d1-
Frequency
1:Analog input A1 or A2
b1-01
Reference
2:Serial Com - RS-422/485
Selection
3:Option board
4:Pulse Input (Terminal RP)
0:Operator - RUN and STOP
Run
keys
b1-02
Command
1:Terminals - Digital Inputs
Selection
2:Serial Com - RS-422/485
3:Option board connected
22
Description
all
parameters
to
values
Par.
Name
Selects the stopping method
when the run command is
removed.
Stopping
0:Ramp to Stop
b1-03
Method
1:Coast to Stop
Selection
2:DC Injection Braking to Stop
3:Coast with Timer (a new run
command is ignored if received
before the timer expires)
Reverse
0:Reverse enabled
b1-04
Operation
1:Reverse prohibited
Selection
Switches
Phase
order.
b1-14
Order
0:Standard
Selection
1:Switch phase order
DC Injection Braking
DC
Sets the frequency at which DC
Injection
Injection Braking starts when
b2-01
Braking
Ramp to Stop (b1-03 = 0) is
Start
Fre-
selected. If b2-01< E1-09, DC
quency
Injection Braking starts at E1-09.
Sets the DC Injection Braking
DC
current as a percentage of the
Injection
b2-02
drive rated current.
Braking
In OLV the DC excitation current
Current
is determined by E2-03.
DC Inj.
Braking
Sets the time of DC Injection
Time/DC
Braking at start in units of 0.01
b2-03
Excitation
seconds. Disabled when set to
Time
at
0.00 seconds.
Start
DC Inj.
Sets the DC Injection Braking
Braking
b2-04
time at stop. Disabled when set
Time
at
to 0.00 seconds.
Stop
Acceleration/ Deceleration
Sets the acceleration time 1
Accel
C1-01
from 0 to the max. output fre-
Time 1
quency.
Sets the deceleration time 2
Decel
C1-02
from the max. output frequency
Time 1
to 0.
I67E-EN
Description
the
output
phase
V1000 Quick Start Guide

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis