• Once the LON IF-module has been configured and switched online, a double
arrow appears on the pump display (Fig. 6, pos. 1) to indicate the existing
communication. Local operation of the pump with the red button is disabled.
Exceptions:
• Settings for the peak load or main/standby operation double pump functions
• You can access the "Id" menu by turning the red button. A network message
is sent in which the Neuron ID is transmitted by pressing the red button in this
menu item.
NOTE: The IF-module LON no longer works if there is an interruption to the
power supply of the pump. All input network variables (nvi...) are reset to their
default values when the power supply is switched on again.

9 Maintenance

Have maintenance and repair work carried out by qualified skilled
personnel only!
WARNING! Danger from electric shock!
Any danger from electrical current should be ruled out.
The pump should be electrically isolated and secured against unauthorised
switch-on during any maintenance or repair work.
NOTE: The IF-module LON has a program memory which can be deleted and
overwritten to allow subsequent software updates to be loaded into this
memory via the LON bus.
Installation and operating instructions Wilo-Control IF-module LON / IF-module Stratos LON