Object status
network output SNVT_obj_status nvoStatus
This output network variable provides status information on the individual
objects. The information is bit-coded. All bits are deleted after a reset.
Value range
Bit
invalid_id
invalid_request
disabled
electrical_fault
unable_to_measure
comm_failure
manual_control
in_alarm
report_mask
Installation and operating instructions Wilo-Control IF-module LON / IF-module Stratos LON
Function
A non-existent object was addressed.
An unknown request was sent.
The object in concern is switched off.
The pump controller object indicates an electrical error.
The pump controller object cannot communicate with the pump.
For the node object only
The pump controller object is disabled for controlling by the
hardware settings at the pump (ext. off, ext. min, IR monitor)
The pump controller object indicates an error.
Indicates that nvoStatus contains the status mask, i.e. the list of all
supported bits, due to a preceding RQ_REPORT_MASK request.
English