English
Status = 1, value = 200 = 100%.
SCPT reference: SCPTSetpoint (213)
Send heartbeat
network input config SNVT_time_sec nciSndHrtBt
This input configuration network variable defines a clock at which
certain output network variables are automatically sent (nvoPumpCapacity,
nvoEffOpMode, nvoControlMode and nvoPumpStatus). A different network
variable is sent with each clock.
Value range
0.0 – 6553.4 s (in 0.1 s steps). The value 0.0 s switches automatic sending off.
The invalid value 6553.5 s has the same effect as the value 0.0 s.
Default value: 0.0 s (automatic sending switched off)
SCPT reference: SCPTmaxSendTime (49)
Minimum send time
network input config SNVT_time_sec nciMinOutTm
This optional input configuration network variable defines a minimum clock for
the automatic transmission of network variables. The network variables are
normally transmitted automatically if they have changed or if they have been
changed at least by a certain amount. This network variable now has the effect
that two transmission procedures are performed only at the specified interval.
This is used, for example, to reduce the system load. The individual network
variables are sent cyclically.
Value range
0.0 – 6553.4 s (in 0.1 s steps). The value 0.0 s switches off the minimum clock.
The invalid value 6553.5 s has the same effect as the value 0.0 s.
Default value: 0.0 s
SCPT reference: SCPTminSendTime (52)
Object major version
network output config unsigned short nciObjMajVer
This output configuration network variable provides the high byte for the
software version.
SCPT reference: SCPTobjMajVer (167)
Object minor version
network output config unsigned short nciObjMinVer
This output configuration network variable provides the low byte for the
software version.
62
WILO AG 04/2007