Value range
-163.840% – 163.830% (in 0,02% steps). 163.835% is an invalid value.
Transmission
This value is transmitted automatically if it deviates from the value transmitted
last by more than 5% of the value in nroPumpChar.pressMax (with differential
pressure control) or 2% of the value in nroPumpChar.speedMax (with speed
controller). Furthermore, this value is regularly transmitted if the nciSndHrtBt
configuration input was described with a valid clock. This value is also
transmitted if the control mode has been changed by overriding settings or the
connection of an external sensor.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: acknowledged
Effective operating mode
network output SNVT_hvac_mode nvoEffOpMode
This output network variable provides the current operating mode of the pump.
This value corresponds to the setting in the nviPumpOpMode input network
variable, provided a different operating mode has not been forced by local
settings at the pump (ext. off, ext. min or IR monitor).
Value range
Value
HVAC_AUTO
HVAC_MRNG_WRMUP
HVAC_PRE_COOL
HVAC_ECONOMY
HVAC_OFF
HVAC_NUL
Transmission
This value is automatically transmitted whenever a change is made.
Furthermore, this value is transmitted regularly if the nciSndHrtBt configuration
input was described with a valid clock.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: acknowledged
Installation and operating instructions Wilo-Control IF-module LON / IF-module Stratos LON
Function
Normal operation
Warm-up mode
Cooling mode
Energy-saving mode
Offline mode
Invalid
Comments
Setpoint via nviPumpSetpoint
Maximum speed
Maximum speed
Setback operation speed
(pump type specific)
Ext. off or manual operation mode
via IR monitor