English
Maximum status send time
network input config SNVT_elapsed_tm nciMaxStsSendT
This optional input configuration network variable defines a clock at which the
object statuses are automatically sent. The status of the node object and
pump-controller object are sent alternately.
Value range
0d0h0m0s0ms – 0d17h59m59s999ms (in 1 s steps). The value 0d0h0m0s0ms
switches off automatic sending.
Default value: 0d0h0m0s0ms (automatic sending switched off)
SCPT reference: SCPTmaxSendT (22)
Device major version
network output config unsigned short nciDevMajVer
This optional output configuration network variable provides the high byte of
the module version.
SCPT reference: SCPTdevMajVer (165)
Device minor version
network output config unsigned short nciDevMinVer
This optional output configuration network variable provides the low byte of
the module version.
SCPT reference: SCPTdevMinVer (166)
Location label
network input config SNVT_str_asc nciLocation
This optional input configuration network variable can be used to save
information about the installation location of the pump which goes beyond the
information string stored in the Neuron chip, which only consists of 6 Byte.
Value range
Optional NUL-terminated ASCII string of max. 31 bytes length (incl. NUL)
Default value
ASCII string which only consists of NUL ("\0")
SCPT reference: SCPT_location (17)
46
WILO AG 04/2007