Pump override active
network output SNVT_switch nvoPumpOverride
This optional output network variable provides the status of the overriding
settings.
Value range
Status
0
1
255
Transmission
This value is transmitted whenever a change is made.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Runtime
network output SNVT_time_hour nvoRuntime
This optional output network variable provides the operating hours of the
pump, or with double pumps, the time during which at least one pump was
running. The counter is reset to 0 h after 65535 h.
Value range
0 – 65535 h (in 10 h steps), (max. 2730 d or 7.48 a).
Transmission
This value is transmitted whenever a change is made.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Installation and operating instructions Wilo-Control IF-module LON / IF-module Stratos LON
Value
0
200
0 – 255
Function
NORMAL
OVERRIDE
Invalid