The parameter „time" represents the activation duration:
Value 1.....253:
Value 254:
Value 255:
RF:
With the RF parameter, the corresponding switching output will react to the event „Remote
control" (RF).
With the parameter „Time", which is mandatory, the time is indicated for which the output is to
be activated after the RF signal. With the optional third parameter („ENABLE"/„DISABLE"), you
may select whether only the event for „ENABLE" or „DISABLE" should trigger a reaction.
Example:
With the two following commands...
SET OUT1 RF 255 ENABLE #1513
SET OUT2 RF 1 DISABLE #1513
...alarm activation (= „ENABLE") will switch output OUT1 for 1/2 s and alarm deactivation (=
„DISABLE") will switch output OUT2 for 1 s.
All „ALARM ENABLE/DISABLE" events are used for switching the relay, not only
from the RF wireless remote control. This is also possible, e.g via text message and
INCALL (where configured accordingly).
ALARM:
In the ALARM mode, the relay output is switched for the corresponding amount of time.
Example:
Use the following command to switch the 2nd relay for 3 s in case of alarm:
SET OUT2 ALARM 3 #1513
The alarm output reacts to all ALARM events, no matter whether „SILENT" or „NOISE"
operating mode. The relay only switches 1 x in case of alarm.
98
Time in seconds
0.25 seconds
0.5 seconds