Reset to factory settings (LH):
RESET IN1 #1513
Settings for the input (IN1) can be requested via the following command:
TEST IN1 #1513
Timer function:
An optional second parameter can be used to set how long a signal must be pending without
interruption before an alarm is triggered.
SET IN1 <LH/HL/LHL> <time> #1513
The parameter „Time" indicates the time in seconds before an alarm is triggered.
0 = Off (basic position)
1....90 seconds)
Observe that not using a 2nd parameter will not change the time.
SET IN1 LH 5 #1513 Activation of alarm at HIGH after 5 s
SET IN1 HL #1513
The time is displayed in the status text message. The internal time measurement
may be delayed by up to 1 second, so that a set time of 30 s may take up to 31 s
to activate.
Active alarm:
An optional parameter „NOISE" will output an alarm sound via the speaker if activated.
SET IN1 LHL NOISE #1513
This activates the alarm with additional alarm sound output at any change at the input IN1.
100
Activation of alarm at LOW and continued at 5 s