Anomalies related to the plumbing circuit
PROBLEM
No increase in
temperature with
Hydro Insert in
operation
Condensation
in Hydro Insert
Radiators cold in winter
but the Hydro Insert
boils
Hot water in not
provided
The Hydro Insert boils
under "modulation"
that reaches the
temperature set on
the thermostat of the
Hydro Insert
44
1.
Room
thermostat
maximum
2. Temperature sensor defective
3. Control panel defective or
broken
1. Incorrect programming of the
cronothermostat
1. The board is set to automatic
correction of power in proportion
to the temperature
POSSIBLE CAUSE
1. Incorrect combustion
adjustment
2. Hydro Insert/system dirty
3. Insufficient Hydro Insert power
1. Incorrect setting maximum
water temperature in the Hydro
Insert
2. Insufficient fuel consumtion
1. Circulator does not run because
blocked
2. Radiators have air in them
1. Circulator pump blocked
1. It 'been set to a value of
thermostat too high
2. It was set too much power to
the implant.
set
to
1. Reset the thermostat temperature
2. Check the operation of the sensor and replace if
necessary
3. Check the panel and replace if necessary
1. Check the settings of the cronothermostat
1. Contact your Authorized Assistance Center
REMEDY
1. Check parameters
2. Check and clear the Hydro Insert
3. Check that the Hydro Insert is properly sized for the
requirements of the system
1. Set the Hydro Insert to a higher temperature. The
maximum water temperature in the Hydro Insert is 65 °
C and can not be set below 40° C or above 80 ° C. It is
advisable to never adjust the temperature below 60 ° C
to avoid condensation in the Hydro Insert.
Adjust the power of the pump at a higher
temperature to 60 ° C.
2. Contact your Authorized Assistance Center
1. Free up the circulator by removing the plug and
turning the shaft with a screwdriver.
Check the electrical connections of the same,
replace if necessary
2. Vent the radiators
1. Free the circulator pump
1. Lower the temperature in the Hydro Insert
2. Reduce the value of operating power