EN
Operating instructions
Index
Name
(decimal)
126
System
monitor
127
Display text
128
Simulate
measured
value
129
Level
96
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
8 IO-Link
Format
Access
16-bit
R
record
8 x 8 bit
R
8-bit
R/W
unsigned
16-bit
R/W
unsigned
Value
Record
System diagnosis flags
Bit 0
Internal warning
Bit 1
Q1 short-circuit
Bit 2
Q2 short-circuit
Bit 3
QA overload
Bit 4
QA current cannot be set or
excess temperature
Bit 5
Supply voltage for
IO-Link insufficient
Bit 6
Supply voltage for Q1 and Q2
insufficient
Bit 7
Supply voltage for QA insufficient
Bit 8
Temperature of the electronics
too high
Bit 9
Temperature of the display too
high
Bit 10
Measurement poor or conspicu-
ous (warning)
Bit 11
Measurement not possible
Bit 12
Echo curve invalid (measure-
ment not possible)
Bit 13
Device not adapted to the tank
(AutCal still has to be called up)
Bit 14
Other (unknown) error
Bit 15
Reserved (= 0)
String
Current display on the screen,
e.g., 0 mm or 0%
0 Normal
This parameter is volatile. This
measuring
means that the normal measur-
operation
ing operation will always be
started again after the LFP is
1 Simulation
reset.
operation
Read
Current level in millimeters
Write
If simulate measured level is set
to 1, the measured level can be
simulated by writing.
LFP Inox
Description