4 Configuring the analog output

4.1 Automatic signal detection

The sensor can automatically detect which signal is required by means of the connected output load
(see Chapter 9 "Technical data")
The following information applies:
4 mA to 20 mA < 500 ohms at Uv > 15 V
4 mA to 20 mA < 350 ohms at Uv > 12 V
0 V to 10 V > 750 ohms at Uv ≥ 14 V
Configuration
Access the menu QAMENU-Typ using the arrow and the Set pushbuttons and configure Auto?
Note: Automatic signal detection is only active at the initial start. This fuction can be activated
again in the menu QAMENU-Typ with Auto?

4.2 Current output 4-20 mA

Configuration
Set upper limit value (20 mA)
In the QAMENU-QAHIGH menu, set the value to the level height in mm (e.g., 500 mm)
Set lower limit value (4 mA)
In the QAMENU-QALOW menu, set the value to the level height in mm (e.g., 10 mm)
Invert signal
The analog signal can be inverted in the QAPOL menu
Set parameter to QA-Inv in the QxMENU-QAPOL menu
QA-NRM = Analog output signal as configured
QA-INV = Analog output signal is inverted: QAHigh 4 mA and QALow 20 mA
Select electrical signal
Set parameter to 4-20 mA in the QxMENU-QATYP menu

4.3 Voltage output 0-10 V

Configuration
Set upper limit value (10 V)
In the QAMENU-QAHigh menu, set the value to the level height in mm (e.g., 500 mm)
Set lower limit value (0 V)
In the QAMENU-QALow menu, set the value to the level height in mm (e.g., 10 mm)
Invert signal
The analog signal can be inverted in the QAPOL menu
Set parameter to QA-Inv in the QxMenu-QAPOL menu
QA-Nrm = Analog output signal as configured
QA-Inv = Analog output signal is inverted: QAHigh 0 V and QALow 10 V
Select electrical signal
Set parameter to 0-10 V in the QxMenu-QATYP menu
74