LFP Inox
200 % = low sensitivity
○
Value range 20 to 500 %
○
8. Launch EXPRT-Foam-CalMed
!CalOk: Everything has worked, continue with step 9
○
!faild: Repeat step 5
○
9. Check foam calibration in EXPRT-Foam-FomSta
active: Foam commissioning was completed successfully.
○
inactiv: Commissioning incorrect. Please repeat the process.
○
Notes
Measurement value can be higher
■
Signal quality 1 and 2 are not counted
■
The sensor ends expert modes automatically after 5 minutes of inactivity on the display.
■
Configuration (foam teach) does not take place in the following processes:
■
Changing the probe length
○
Changing the measuring mode
○
Changing the teach-in depth
○
Performing AutCal
○
If you are encountering problems, see Chapter 7 "Troubleshooting".
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
2 Commissioning the LFP
EN
Operating instructions
67