LFP Inox
3.1 Normally open with adjustable hysteresis
Applications
Dry run protection
■
Empty signal
■
Configuration
Configure the Qx switching output as normally open
■
Set parameter to Qx_Hno in the QxMENU-OUx menu
○
Set the switching point
■
In the QxMENU-SPx menu, set the value to the level height in mm (e.g., 500 mm)
○
Set the reset switching point
■
In the QxMENU-RPx menu, set the value to the level height in mm (e.g., 450 mm)
○
Select electrical property (NPN/PNP/DRV (Push-Pull))
■
Select parameters in the QxMENU-TYPx menu
○
The following information applies:
○
Qx-PNP = Switching output in PNP circuit
▫
Qx-NPN = Switching output in NPN circuit
▫
Qx-Drv = Switching output in Push-Pull function
▫
Switching output behavior
Level
SP
RP
activ
inactiv
Switching output
Normally open/HNO
Pulldown only.
1)
Pullup only
2)
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
3 Configuring the switching outputs
t
Error signal
PNP
Active
Uv
Inactive
0 V
1)
NPN
DRV
0 V
Uv (PNP switched)
Uv
2)
0 V (NPN switched)
EN
Operating instructions
Error status
Inactive
69