9.6 Electrical connection values

Supply voltage
1) 2)
Power consumption
Initialization time
Protection class
Connection type
Hysteresis
Output signal
1)
Signal voltage HIGH
Signal voltage LOW
Output current
Inductive load
Capacitive load
Temperature drift
Output load
Lower signal level
Upper signal level
EMC
All connections are reverse polarity protected. All outputs are overload and short-circuit protected.
1)
For the voltage supply, use an energy-limited circuit in accordance with UL61010-1 2nd Ed., Section 9.3; for indoor use
2)
only

9.7 Environmental conditions

Ambient temperature, operation
Ambient temperature, storage
Ambient temperature, coaxial cable
According to UL-Listing: Pollution degree 3 ((UL61010-1: 2012-05); maximum relative humidity 80 % for temperatures up
1)
to 31 °C ; maximum operating altitude of 3.000 m above sea level
100
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
9 Technical data
12 V DC to 30 V DC
≤ 100 mA at 24 V without output load
≤ 5 s
III
M12 x 1 (5-pin)
Min. 3 mm, freely adjustable
4 mA to 20 mA/0 V to 10 V automatically switchable depending on
output load
1)
PNP transistor output (Q1) and 1 PNP/NPN transistor output (Q2)
switchable
Uv -2 V
≤ 2 V
< 100 mA
< 1 H
100 nF
< 0.1 mm/K
4 mA to 20 mA < 500 ohms at Uv > 15 V
4 mA to 20 mA < 350 ohms at Uv > 12 V
0 V to 10 V > 750 ohms at Uv ≥ 14 V
3.8 mA to 4 mA
20 mA to 20.5 mA
EN 61326-1:2006, 2004/108/EC