LFP Inox
Parameter
EXPRT
TrsHld
Offset
MaxCol
MeasMd
Length
CalRng
CbILen
Lock
Unit
Foam
CalEmp
CalMed
FomSta
Limit
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
6 Menu overview
Description
See chapter „5.1 Expert Mode"
This value describes a factor which determines how strong an echo has to be
in order to be recognized by the device. The value range lies between 20 % and
500 %. The default is 100 % in this case. Only shown if password entered.
20 % = high sensitivity
●
100 % = standard
●
500 % = low sensitivity
●
See chapter „5.10 Setting an Offset"
See chapter „5.2 Filtering the measured values"
Measuring mode
HiSpd: max. Length = 2,005 mm, response time < 400 ms
●
HiSpd: max. Length = 6,005 mm, response time < 2,800 ms
●
(more stable measured values, recommended for liquids with low DKs and
where the TrsHld is < 70)
mode-1: not supported, deactivates current AutCal/foam calibration
●
See chapter „5.4 Configuring the probe length"
See chapter „5.4 Configuring the probe length"
See chapter „5.7 Configuring coaxial cable length"
See chapter „5.8 Enabling menu protection"
See chapter „5.9 Selection the displayed units (Millimeter/Inch)"
See chapter „2.3 Foam commissioning (with factory settings)"
See chapter „2.3 Foam commissioning (with factory settings)"
See chapter „2.3 Foam commissioning (with factory settings)"
Status of the foam calibration, read-only access
inactv: CalEmp and/or CalMed not successful or not performed.
●
Foam treatment inactive.
active: Foam treatment active
●
Limit between foam and fluid
Range: 20 to 100 %
●
Factory setting: 90 %
●
Medium surface: 90 %
●
Foam surface: < 90 %
●
When measuring the foam surface, it may be necessary to reduce the limit. If the
sensor displays a limit value that is too low, it is necessary to reduce the limit.
EN
Operating instructions
85