5.6 Evaluating the signal quality

Parameters describe the quality of the measuring signal.
Log in to expert mode (Please see „5.1 Expert Mode")
SigQa1
Characteristic for the robustness of the TrsHld setting
Not active in foam mode. The displayed value is only valid if the sensor is displaying the correct
level value.
Value range: 0 to 100%
Good signal: > 40% (a high pulse reserve is provided with the current TrsHld setting.)
Measures: Reduce EXPRT-Config-TrsHld to increase SigQa1.
Note:
Changing TrsHld will have an impact on SigQa2 and SigQa3.
If a satisfactory SigQa1 value cannot be achieved by adjusting TrsHld in conjunction with the
SigQa values, the installation condition must be checked. Using a coaxial tube improves signal
detection, particularly in media with low DK values (e.g., oil).
SigQa2
Characteristic for the robustness of echo pulse detection in relation to interference pulses
Not active in foam mode. The displayed value is only valid if the sensor displays the correct level
value.
Value range: 0 to 100 %
Good signal: > 50 %
Measures: Launch AutCal; check installation conditions; remove buildup from the probe and the
process connection
SigQa3
Characteristic for signal noise and electromagnetic interference
Value range: 0 to 100%
Good signal: > 75%
Poor signal: < 50%
Not active in foam mode. The displayed value is only valid if the sensor displays the correct level
value.
Value range: 0 to 100 %
Measures:
Increase EXPRT-Config-TrsHld
EXPRT-Config-MeasMd = HiAcc
Improve filtering
Switch on filter
Reduce EXPRT-Config-MaxCol
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice