5.10 Setting an Offset

Value shown on display can include an offset. This is useful if it is necessary to see the liquid level
from the bottom of a tank instead of from the probe end.
Configuration:
Log in to expert mode (Please see „5.1 Expert Mode")
Set offset in Menu EXPRT-Config-Offset (0...3000mm)
Please see picture below
Note:
If the parameter Offset will be changed then the parameters SPx/RPx/FLx/FHx/
QaLow/QaHigh will be automatically adjusted.
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
5 Advanced functions
QALOW / QAHIGH
SPx / RPx
FHx / FIx
can be set only in this zone
O: Offset
L: Probe length
M: Measuring length
IA: Inactive area at process connection
IAE: inactive area probe end