Herunterladen Inhalt Inhalt Diese Seite drucken

SICK LFP inox Betriebsanleitung Seite 95

Tdr-füllstandsensor
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

LFP Inox
Index
Name
(decimal)
74
QAType
75
QAFailCur-
rent
76
POLA
8014485/YE12/2014-08-20 © SICK AG • Level sensors • Germany • Subject to change without notice
8 IO-Link
Format
Access
8-bit
R/W
unsigned
8-bit
R/W
unsigned
8-bit
R/W
unsigned
Value
0 4 mA to
Switchover, current/voltage
20 mA
output
1 0 V to
When this parameter is being
10 V
read, the type that has most
recently been decided upon is al-
2 Auto
ways read (0 or 1). Despite this,
Detect
the decision is made again every
time the device is reset.
3 Auto V
4 Auto A
0 3.5 mA
Determining fault current
1 21.5 mA
This parameter has no function
in voltage mode
0 Normal
Inversion of the analog output
1 Inverse
Normal:
QALow is at the 4 mA or 0 V
point and QAHigh describes
the 20 mA or 10 V point
Inverse:
QALow is at the 20 mA or
10 V point and QAHigh describes
the 4 mA or 0 V point
EN
Operating instructions
Description
95

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis