Electrical wiring
4 Capacity code setting (DSW3). No setting is required, due to setting before shipment. This switch is used for setting the capacity
code which corresponds to the Horse Power of the indoor unit.
Horsepower
0.6
ON
Setting
position
1 2 3 4 5 6
5 Refrigerant cycle number setting (RSW2 & DSW5). Setting is required. Setting positions before shipment are all OFF.
Refrigerant cycle number setting
DSW5 (Tens digit)
ON
OFF
Before shipment, DSW5 and RSW2 are set to "0". Max. 64 cycles are available to set when all
the equipment to be connected are corresponding to H-LINK ΙΙ. Max. 16 cycles when the units
corresponding/ non-corresponding to H-LINK ΙΙ are combined.
6 Fuse recover (DSW7). (This dip switch is located on PCB1.)
* In the case of applying high voltage to the terminal 1 and 2 of
TB2, the fuse (0.5A) on the PCB is cut. In such a case, firstly
reconnect the wirings correctly to TB2, and then turn on Number
1 pin.
Factory setting
ON
1 2
7 Optional function setting (DSW2). No setting is required. Set-
ting positions before shipment are all OFF.
Factory setting
N O T E
•
In order to identify one indoor unit with its own wireless re-
mote control, set DSW2 pin3 ON and set the wireless remote
control at "b" mode. For more information, please refer to the
corresponding Intallation and Operation Manual.
•
When using a wireless remote controller, no additional recei-
vers are required for individual operation.
•
For simultaneous operation it is required:
Option 1: PC-ARF remote control.
Option 2: In the case of wireless operation with PC-LH3B,
PC-ALHZF receiver kit is necessary.
In both options change SW2 to wired setting.
38
0.8
1.0
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
Setting
position
High voltage
ON
1 2
Distinguish of indoor units
using wireless remote
control
PMML0292A rev.2 - 09/2015 - P5416572
1.5
2.0
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
RSW2 (Units digit)
Set by inserting
slotted screwdriver
into the groove.
8 Remote control switch setting (SW2). The setting before shi-
pment is "Wireless".
* In case of using the wired remote control (PC-ARF) and the
receiver kit (PC-ALHZ), set the SW2 to "Wired". If not, the opera-
tion is not available. Connect the remote control switch cables to
terminals A and B at the terminal board TB2.
Factory setting
N O T E
■
•
The "
" mark indicates position of dip switches. Figures show
setting before shipment.
•
When the unit number and the refrigerant cycle are set, record
the unit number and refrigerant cycle to facilitate maintenance
and servicing activities thereafter.
•
Turn OFF all the power supply of the indoor unit and the out-
door unit before Dip Switch setting. If not, the setting is invalid.
•
In case of using the wired remote control or receiver kit PC-
ALHZF set the SW2 to "Wired".
9 (SW1) No settings are required. Factory setting:
10 (DSW9) No settings are required. Factory setting:
2.5
3.0
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
Ex.) Set at number 5 cycle
DSW5
ON
OFF
Set all pins OFF
RSW2
Set at "5"
Wired remote control
ON
1
2
4.0
ON
1 2 3 4 5 6