Error during the inspection of the UserPrmData
Error code 3
A selected combination of functions is not permitted. Description using reason
for error.
Reason for error
1
2
6
8
10
11
12
Error during the inspection of the CfgData
Error code 2
A byte in the CfgData is incorrect. The reason for the error describes the
CfgData byte in which the error was detected (offset of the faulty byte+1)
Error code 5
The lengths of the digital outputs (in bytes) that were calculated from the
CfgData are incorrect. The reason for error contains the expected byte length.
Error code 6
The lengths of the digital inputs (in bytes) that were calculated using the
CfgData are incorrect. The reason for error contains the expected byte length.
Error code 7
Displays various errors during the inspection of the CfgData. The reason for er-
ror describes the error.
Reason for error
1
2
3
4
64
Description
In synchronous mode, setting the reaction to DP er-
rors to "Outputs unchanged" is not permitted
The DPV1-MSAC-C1 connection was activated by
the master, but no DPV1-MSAC_C1 connection is
defined
Multi-configurator mode is not permitted if the in-
spection of the CfgData is disabled
Synchronous mode may only be activated if at least
one DP output byte is configured
The optimized input cycle is only possible in syn-
chronous mode
The length of the DP buffer exceeds the size of the
DP RAM in the Profibus Asic
Fast FreeRun mode must not be activated at the sa-
me time as synchronous mode
Description
Length of the received CfgData is incorrect
Syntax of the received CfgData is incorrect
Length of the DP input data that was calculated
from the CfgData is too long
Length of the DP output data that was calculated
from the CfgData is too long