Field bus status
The field bus status LEDs indicate the operating status of the field bus. The Pro-
LEDs
fibus functions are indicated by the LEDs „I/O RUN", „BF" and „DIA"
I/O
RUN
on
on
off
off
off
Profibus confi-
guration data er-
DIA
ror
1 pulse
2 pulses
Displayed ser-
A detailed description of the Service Codes that can be displayed can be found
vice codes
in the "Troubleshooting" chapter of your power source operating instructions.
20
BF
DIA
Cause
off
off
„RUN" operating status
Inputs are read and out-
puts set
on
off,
Field bus activity. Slave
fla-
not yet configured
shing
Field bus error and how
outputs react:
-
-
off
off
Terminal bus cycle syn-
chronous with DP watch-
dog switched off, no da-
ta exchange
on
on
No bus activity
on
off,
Bus error, reaction: ter-
fla-
minal bus cycle is stop-
shing
ped
Error ar-
gument
Cause
0 pulses
Insufficient DP-Cfg data
received
n pulses
Faulty DP-Cfg data-byte
(n>0)
0 pulses
Insufficient User-Prm
data received
n pulses
Faulty User-Prm data
(n>0)
go to 0
remain constant
Remedy
Correct function. No re-
medial action necessary
Start master
Check parameters (dia-
gnostic data, DIA-LED)
Check configuration
(diagnostic data, DIA-
LED)
Start master
Check parameters (dia-
gnostic data, DIA-LED)
Check configuration
(diagnostic data, DIA-
LED)
PLC is in „Stop". Start
PLC
Start master
Check bus cable
Start master
Check parameters (dia-
gnostic data, DIA-LED)
Check configuration
(diagnostic data, DIA-
LED)
Remedy
Check DP configuration
Check DP User parame-
ters