9.3 Miscellaneous faults
Fault
Position skips
by the measuring
system
Printed in the Federal Republic of Germany
08/31/2017
Cause
Solution
Vibrations, impacts and shocks, e.g. on presses, are
dampened with so-called "shock modules". If the error
Strong vibrations
occurs
measuring system must be replaced.
Isolated flanges made of plastic may help against
electrical faults, as well as cables with twisted pair wires
Electrical faults
for data and supply. The shielding and line routing must
EMC
be executed in accordance with the Equipment Mounting
Directives for the respective field bus system.
Extreme axial and
Couplings prevent mechanical stress on the shaft. If the
radial load on the
error still occurs despite these measures, the measuring
shaft may result in a
system must be replaced.
scanning defect.
TR - ECE - BA - DGB - 0105 - 03
repeatedly
despite
these
 TR-Electronic GmbH 2013, All Rights Reserved
measures,
the