Compressor Cut-Out; Fan Overload - CLIVET MSAN 81 Anleitung Zur Installation, Bedienung Und Wartung

Verflüssigersätze in wärmepumpenausführung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 67

COMPRESSOR CUT-OUT

COMPRESSOR CUT-OUT
YES
Compressor discharge
temperature within limits?
Notes
1) Measure, using a thermometer in direct contact, the temperature of the compression line at the position of the compressor
safety thermostat. A correct refrigerant charge corresponds to a maximum temperature of 85°C/90°C.
Higher temperatures mean excessive superheating of the inlet gas; check the right operation of the expansion device.
2) The thermostat inside the compressor is activated at a temperature of around 135°C. Temperatures lower than 100°C must
correspond to a closed contact and the enabling of the operation of the compressor.

FAN OVERLOAD

YES
Unit working
FAN OVERLOAD
Motor intact?
Unit working
NO
Check parameters, e.g.:
superheating, refrigerant
charge, etc.
NO
Check for possible
blockages on exchanger
Check the blades are not
obstructed
Check electric windings
58