4. Functions and options
Thermostat function (Function block 1 ... 5):
Arrangement/Options/Thermo1 (...10)
selection: „Yes", „No"
factory setting: „No"
Arrangement/adj. values/Th1(...10)on
adjustment range: - 40,0 ... 250,0 °C
factory setting: 40,0 °C
Arrangement/adj. values/Th1(...10)off
adjustment range: - 40,0 ... 250,0 °C
factory setting: 45,0 °C
Arrangement/Expert/Sen-Th1 (...10)
adjustment range: 1 ... 10
factory setting: 3 (...10)
DT-function (function block 1 ... 5):
Arrangement/Options/DT-func 5 (...9)
selection: „Yes", „No"
factory setting: „No"
Arrangement/adj. values/DT5(...9)on
adjustment range: 1,0 ... 50,0 K
factory setting: 5,0 K
Arrangement/adj. values/DT5(...9)off
adjustment range: 0,5 ... 50,0 K
factory setting: 3,0 K
Arrangement/Expert/Sen 1-DT5(...9)
adjustment range: 1 ... 10
factory setting: 3 (...10)
Arrangement/Expert/Sen 2-DT5(...9)
adjustment range: 1 ... 10
factory setting: 4 (...10)
The relay allocated to the function block is switched on,
when the adjusted switch-on temperature (Th(x)on) is
reached. It is switched off when the adjusted switch-off
temperature (Th(x)off) is reached. The switching con-
ditions of all other activated functions of the function
block have to be fulfilled as well.
Allocate the reference sensor in the expert menu.
Adjust the maximum temperature limitation with Th(x)off
> Th(x)on and the minimum temperature limitation with
Th(x)on > Th(x)off. The temperatures cannot be set to
an identical value.
The relay allocated to the function block is switched on
as soon as the adjusted switch-on temperature (DTh(x)
on) is reached. It is switched off as soon as the adju-
sted switch-off temperature (DTh(x)off) is reached. The
switching conditions of all other activated functions of
the function block have to be fulfilled as well.
Adjust the reference sensor in the expert menu.
101