Information Regarding Ul; Short Circuit Current Rating; Branch Circuit Protection - SEW-Eurodrive MOVIDRIVE system MDX9 Serie Betriebsanleitung

Applikationsumrichter
Inhaltsverzeichnis

Werbung

Installation
4

Information Regarding UL

4.14
Information Regarding UL
4.14.1
Field wiring power terminals
MDX9.A-....-5.3-...
0020 - 0160
0240 - 0320
0460 - 0750
0910 - 1490
MDX9.A-....-2.3-...
0070 - 0140
0213 - 0290
0420 - 0570
0840 - 1080
All modules
4.14.2

Short circuit current rating

4.14.3

Branch circuit protection

102
Betriebsanleitung – MOVIDRIVE
HINWEIS
The UL-certification does not apply to operation on voltage supply systems with a
non-grounded star point (IT systems).
HINWEIS
Use only tested units with a limited output voltage (V
output current (I
= 8 A) as an external DC 24 V voltage source.
max
Use 60/75 °C copper wire only.
Tighten terminals to in-lbs (Nm) as follows:
Line connection
X1
4.43 – 7.08 (0.5 – 0.8)
Wire sizes 14 – 12 AWG
X1
15.05 – 15.93 (1.7 – 1.8)
X1
75.2 – 84.1 (8.5 – 9.5)
X1
159.3 – 194.7 (18 – 22)
Line connection
X1
4.43 – 7.08 (0.5 – 0.8)
Wire sizes 14 – 12 AWG
X1
15.05 – 15.93 (1.7 – 1.8)
X1
75.2 – 84.1 (8.5 – 9.5)
X1
159.3 – 194.7 (18 – 22)
Suitable for use on a circuit capable of delivering not more than
5,000 rms symmetrical amperes when protected by fuses, circuit breakers and Ty-
pe E combination motor controllers as described in the tables below.
10,000 rms symmetrical amperes when protected by fuses, circuit breakers and
Type E combination motor controllers as described in the tables below.
65,000 rms symmetrical amperes when protected by fuses, circuit breakers and
Type E combination motor controllers as described in the tables below.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
If you use cable cross sections that are dimensioned for a smaller current than the
rated current of the unit, make sure that the fuse is dimensioned for the used cable
cross section.
®
system
Tightening torque in-lbs (Nm)
Motor and braking resistor terminals
X2
X2
X2
X2
Motor and braking resistor terminals
X2
X2
X2
X2
PE connection
M4: 8.85 – 10.62 (1.0 – 1.2)
M6: 26.55 – 35.4 (3.0 – 4.0
= DC  30  V) and limited
max
4.43 – 7.08 (0.5 – 0.8)
Wire sizes 14 – 12 AWG
15.05 – 15.93 (1.7 – 1.8)
75.2 – 84.1 (8.5 – 9.5)
159.3 – 194.7 (18 – 22)
4.43 – 7.08 (0.5 – 0.8)
Wire sizes 14 – 12 AWG
15.05 – 15.93 (1.7 – 1.8)
75.2 – 84.1 (8.5 – 9.5)
159.3 – 194.7 (18 – 22)