BMD 1E _ _ - _ _ _ _ / _ _ _ -NH5...
Microwave Positioning Sensor
5
Object directory (continued)
5.4
Explanations for the 2XXX
manufacturer-specific objects
5.4.1

0x2300 Custom Manufacturer Name

This object may contain a customer-specific manufacturer
name for a special manufacture. The standard value is
Custom.
5.4.2

0x2302 Custom Serial Number

This object may contain a customer-specific serial number
for a special manufacture. The standard value is Custom.
5.4.3

0x2303 Custom Device Name

This object may contain a customer-specific device name
for a special manufacture. The standard value is Custom.
5.4.4

0x2304 Custom Order Code

This object may contain a customer-specific order code for
a special manufacture. The standard value is Custom.
5.4.5

0x2305 Custom ID

This object may contain a customer-specific CANopen ID
for a special manufacture. The standard value is Custom.
5.4.6

0x2600 Manufacturer Name

This object contains the manufacturer name Balluff GmbH.
5.4.7

0x2601 Balluff Device Name

This object contains the Balluff device name BMD-
CANopen.
5.4.8

0x2602 Balluff Serial Number

This object contains the Balluff serial number
YYMMDD000SSSSS CC.
5.4.9

0x2603 Balluff Part Number

This object contains the Balluff part number, e.g.
BMD 1EAA-1500/080-NH560A-LV001-KS288.

5.4.10 0x2604 Balluff Order Code

This object contains the Balluff order code: "BMD0000"
20
english

5.4.11 0x2900 Bus Termination

The BMD CANopen has an internal bus termination (120 Ω
resitor). To turn the bus termination on or off the value of
the 0x2900 Bus Termination Object must be set as follows:
0x2900 Bus Termination
Object Value
0x00
0x01
Tab. 5-4:
Bus termination states
In the delivery state, the bus termination is off, which
means that the resistor is switched off.
An incorrect turning on or off of the bus
termination can result in loss of the bus
signal.

5.4.12 0x2901 Temperature Values

The 0x2901 Temperature Values object can be used to
read out the internal temperature of the sensor. In addition
to the current temperature value, the sensor also stores
the maximum and minimum temperature since the device
started up. All temperature values are indicated with an
offset of 40 °K. A decimal value of 40 thus corresponds to
0 °C.
Objects
0x2901:0 Maximum subindex
0x2901:1 Current internal temperature (40 = 0 °C)
0x2901:2 Max. internal temperature since device
startup (40 = 0 °C)
0x2901:3 Min. internal temperature since device
startup (40 = 0 °C)
Tab. 5-5:
Temperature value subindices
Resolution, temperature:
Accuracy, temperature:
State of the
bus termination
off
on
Remarks
1 Kelvin
±5 Kelvin