MPF 16-22
GB
1
4.5 U
SING THE GENERATOR
Before powering any utility, leave the engine to run
without applied load for at least five minutes so that it
gradually reaches the operating temperature. This will
guarantee longer life of the engine and eliminate the risk
of seizures.
Each generator is equipped with the following outlets:
- A three-phase outlet, EC 32A 400V - 3P+N+GND, from
which all the available power can be drawn.
- A three-phase outlet, EC 16A 400V - 3P+N+GND
- Two single-phase outlets EC 16A 230V - 2P+GND
The available power is as indicated on the adhesive label
carrying the technical characteristics / ixed on the
machine and shown in detail in the table of technical
characteristics paragraph 2.4.
utilities connected to the generator must never exceed
the continuous power value of the generator.
4.6 S
TOPPING
The generator is stopped by turning the ignition key
completely anticlockwise (ref. 1) to the STOP position.
Before stopping it, it is recommended to run it for a few
minutes without applied load so that the internal
temperatures of the engine and alternator are gradually
reduced.
GB
- 22
The sum of absorption of all the
4.7 E
MERGENCY STOP
For an emergency stop of the generator press the
mushroom-head emergency stop button.
Having removed the causes that determined the need for
an emergency stop, release the emergency stop button
in order to return to the operating conditions.
5 PROTECTIONS AND WARNING SIGNALS
The generators are equipped with a series of protections
which safeguard it against improper use and faults which
may compromise integrity.
5.1 P
ROTECTION AGAINST SHORT
See par.2.3 "Table of tecnical characteristics"
For protection against short-circuits and overloads,
the generators have been fitted with magnetothermal
and differential switches which trip, cutting the power,
if there is an overload condition on the alternator or a
short-circuit.
Before restoring the power by returning the
magnetothermal switch lever to the ON position remove
the cause of the fault.
A main differential magnetothermal switch cuts the
power to all the outlets in the event of a short-circuit,
overload and current leakage to earth.
A magnetothermal protection switch at the low-power
outlets,breaks the circuit if a current greater than the
rated current is drawn by the outlets.
G
-
CIRCUIT AND OVERLOAD