Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIMOVERT MASTERDRIVES Betriebsanleitung Seite 194

Vorschau ausblenden Andere Handbücher für SIMOVERT MASTERDRIVES:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Connecting-up
Maximum
connectable cross-
sections, screw
connection,
tightening torque
X1 – Mains
connection, DC link
connection
U1 V1 W1 PE1 C
L1 L2 L3
X2 – Motor
connection
T1 T2 T3
U2 V2 W2 PE2
7-6
Downloaded from
www.Manualslib.com
Type
Order number
A
6SE702_-__A__
B
6SE702_-__B__
C
6SE702_-__C__
D
6SE702_-__D__
Table 7-2
The mains and DC link connections are located on the top section of
the unit on a joint terminal block.
Terminal
1
2
D
3
L+
L-
4
5
6
Terminal 1 is at the left when installed.
Table 7-3
The motor connection is located at the bottom of the unit.
Terminal
1
2
3
4
Terminal 1 is at the left when installed.
Table 7-4
manuals search engine
Finely-stranded
mm²
AWG
1.5 to 10
12 to 6
1.5 to 10
12 to 6
4 to 16
10 to 4
10 to 35
6 to 2
Maximum connectable cross-sections
Designation
Meaning
U1 / L1
Phase U1 / L1
V1 / L2
Phase V1 / L2
W1 / L3
Phase W1 / L3
PE1
Protective conductor
connection
C / L+
DC link voltage +
D / L-
DC link voltage -
Mains, DC link connection
Designation
Meaning
U2 / T1
Phase U2 / T1
V2 / T2
Phase V2 / T2
W2 / T3
Phase W2 / T3
Protective conductor
PE2
connection
Motor connection
Operating Instructions
08.2009
Multi-stranded,
Tightening
solid
torque
mm²
AWG
Nm
2.5 to 16
12 to 4
2
2.5 to 16
12 to 4
2
10 to 25
6 to 2
2
10 to 50
6 to 0
3.5
Range
3AC 380 - 480 V
3AC 380 - 480 V
3AC 380 - 480 V
DC 510 - 650 V
DC 510 - 650 V
Range
3AC 0 - 480 V
3AC 0 - 480 V
3AC 0 - 480 V
6SE7087-6JD50