Chapter 5 Parameter Settings

5-1 Monitor parameters
No.
D00 – Output frequency monitor
0
1
D01 – Frequency setting monitor
0
1
D02 – Current monitor
0
1
2
3
4
7
8
9
D03 – Voltage monitor
0
1
2
3
D04 – Sequence status
0-3
4-7
D05 – Minor fault monitor
0
1
Downloaded from
www.Manualslib.com
Parameter
Unit
Output frequency in Hz
Hz
Output frequency in %
%
Set frequency in Hz
Hz
Set frequency in %
%
Output current (Amps)
A
Output current (%)
%
Overload (OL-1) monitor
%
Motor overload (OL-3)
%
monitor
Heatsink temperature
°C
U phase output current
A
amps
V phase output current
A
amps
W phase output current
A
amps
DC voltage
V
Output voltage (command)
V
Output power
kW
Carrier frequency
Sequence status-Input 1
to 4
Sequence status-Output 1
to 4
Minor fault failure monitor
Hardware detection fault
status
A state of ON/ off of the internal sequence data is indicated as follows.
(For V24-O P 1)
AFS2
AFS3
PROG
CFS
COP
BRAKE
EXC
JOG
Sequence Input(D04-0)
manuals search engine
will display when the drive is in standby.
displays while the DC brake is in action.
is displayed during pick up.
The currently selected frequency setting value is displayed.
The max. frequency is displayed as 100%.
will display when the drive is in standby.
The motor rated current is displayed as 100%.
OL-1 functions when this value reaches 100%.
The OL-3 operates when at 100%.
Depending on the capacity, OHT.1 functions at 95°C or 120°C or more.
will display when the gate is closed.
The correct value is not displayed during pick-up or during automatic tuning.
Displays the voltage of the DC link circuit in the main circuit.
Displays output voltage command. The display may differ from the actual output
voltage. It depends on the power supply voltage.
closed.
Displays the inverter's output power.
The current carrier frequency is displayed.
The ON/OFF state of the internal sequence data will display.
The correspondence of each LED/LCD segment and signal is shown in the next
page.
The internal minor fault status will display.
The status of the fault signal detected by the hardware is displayed.
(For V24-O P2)
AFS1
CPASS
IPASS
S7
CSEL
MBRK_ans
EMS
BUP
RESET
FDW
RUN
REV
EN-26
Remarks
will display when the gate is
will display when the gate is closed.
PICK
S5
S6
AUXDV
IVLM
BDW
S0
S1
FUP
S2
SE
S3
Sequence Input(D04-1)