Herunterladen Inhalt Inhalt Diese Seite drucken

GE VAT300 Kurzanleitung Seite 25

Vorschau ausblenden Andere Handbücher für VAT300:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69
7) During automatic tuning execution
8) Normal completion of automatic tuning
9) Abnormal completion of automatic tuning
4-6-2 Automatic tuning error messages
If automatic tuning ends abnormally, the following message will appear. Investigate and confirm the
state following the error code.
Downloaded from
www.Manualslib.com
The progression state can be confirmed with D22-0.
(F o r V 2 4 -O P 1 )
When the automatic tuning ends normally, the "LCL" LED will change from a flicker to a stable
light. The "RUN" LED will change from a stable light to the OFF state.
Refer to section 4-5 for the adjustment items.
If automatic tuning ends abnormally, the "FLT" LED will turn ON and a message will appear.
Investigate and check according to the error codes.
Refer to section 4-6-2 for details on the error codes.
E00:ATT-n (for U30 V24OP1),
No.
n=1
The motor may not be connected correctly.
Check the connection.
The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
n=2
The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
n=3
The load and machine may not be separated.
Separate the load and machine.
Lengthen the acceleration time (A01-0).
Lengthen the deceleration time (A01-1).
If the motor vibrates, adjust the torque stabilizing gain (B18-2).
Normally, the default value (1.00) is set, but increase the setting value in increments of
approx. 0.05 according to the state of hunting. Please return to regulated value (1.00) of a
set value once, and reduce it by carving about 0.05 when the hunting phenomenon is not
controlled even in case of maximum value (4.00) .
n=4
The load and machine may not be separated.
Separate the load and machine.
If the motor vibrates, increase the torque stabilizing gain (B18-2).
Normally, the default value (1.00) is set, but increase the setting value in increments of
approx. 0.05 according to the state of hunting. Please return to regulated value (1.00) of a
set value once, and reduce it by carving about 0.05 when the hunting phenomenon is not
controlled even in case of maximum value (4.00) .
n=5
When the motor does not stop
Increase the acceleration/deceleration time (A01-0, A01-1).
When the motor does stop
The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
n=6
The B00 and B01 parameters may not be set correctly.
Check the parameter setting.
Indicates that the output voltage did not stabilize for 1 second or more during magnetic pole
n=8
position estimation for the PM motor.
n=9
Indicates that the PM motor magnetic pole estimation did not end normally even after
retrying three times.
manuals search engine
(F o r V 2 4 -O P 2 )
U p p e r le ve l :T h e ste p s re q u ire d fo r tu n in g a re
L o w e r le ve l :T h e fin is h e d s te p s a re in d ic a te d (lit).
(for U30 V24OP2) n:Automatic tuning step
Cause and remedy
EN-23
in d ica te d (lit).
T h e s te p c u rre n tly b e in g e xe c u te d is
in d ica te d w ith a flic k e r.

Werbung

Inhaltsverzeichnis
loading