Herunterladen Inhalt Inhalt Diese Seite drucken

Operation; Description Of The System - Grundfos Vaccuperm VGS-141 Montage- Und Betriebsanleitung

Gas dosing system
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 27

6. Operation

6.1 Description of the system

4
3
2
1
Fig. 30 Functional scheme VGS-141, -143, -145
Item
Component
1
Line to the injector
2
Differential pressure regulator
3
Electronics (option)
4
Clamp box (option)
5
Servomotor
6
Rate valve
7
Measuring tube
8
Vacuummeter
Sensor for the operation vacuum
9
(option)
10
Line from the vacuum regulator
11
Foot
17
Front hood (17) to take off, with swing-
18
out clear vision flap (18)
The rate valve is not a perfectly closing shut-off
Caution
valve!
5
6
8
7
9
10
11
Description
It regulates the difference of the pressures before and after the rate valve to a
constant value.
Adjusted dosing flow stays constant, even when the injector vacuum fluctuates.
with electronic vacuum sensor (option)
Measuring amplifier for the chlorine concentration Conex
amplifies the signal of the optional measuring cell
Adjusting the desired gas flow
manually with the hand wheel
or
automatically with an electrical servomotor (5) (option)
servomotor can optionally be equipped with a 4 - 20 mA signal input for
proportional control (no further electronics necessary)
Displays the gas flow
with magnetic detection of the floater position (option)
Displays the injector vacuum
with limit contacts (option)
For measuring the vacuum at the inlet of the gas dosing system
Fig. 31 Front hood to take off, with swing-out clear vision flap
17
18
®
®
DIA-2Q or Conex
DIS-2Q
21

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Vaccuperm vgs-143Vaccuperm vgs-145

Inhaltsverzeichnis