Specifications

10. Specifications

10.1

Main unit

Rated supply voltage
Rated frequency
Nominal power consumption
Inrush current
Allowable supply voltage
Allowable momentary
power-off time
Ambient temperature
Ambient humidity
Breakdown voltage (initial)
Insulation resistance (initial)
Insulation
Vibration resistance
Shock resistance
108
100 to 240 V AC
100 to 300 V DC
50/60 Hz
Approx. 5 VA
Approx. 3 W
30 A or less
85 to 264 V AC (85 to 110% of rated supply voltage)
10ms
Accuracy guarantee:
Operation:
Storage:
30 to 85 % RH (at 20 °C) non-condensing
a) enclosure
Between the
isolated circuits:
b) between insulated circuits
2000 V / 1 min
• power supply terminals
• measured current input terminals
Between the
isolated circuits:
100 MΩ or more
Basic insulation:
1.5 mm
clearance /
• RS485 terminals
creepage
distance
10 to 150 Hz (7.5 minutes/cycle)
single amplitude: 0.075 mm (1 h on 3 axes)
10 to 55 Hz (1 minute/cycle)
single amplitude: 0.0375 mm (1 h on 3 axes)
2
Min. 294 m/s
(5 times on 3 axes)
(240 V AC at 25 °C)
(240 V DC at 25 °C)
(240 V AC/DC at 25 °C)
-10 to +55 °C
-25 to +55 °C
-25 to +70 °C
terminals
⇔ all terminals
⇔ other terminals
⇔ other
⇔ other terminals