Communications
Check code (CS)
It is lower than 1 byte in total of all bytes from frame start symbol to data field.
Example: If the transmission command is '68 01 00 00 00 00 00 68 11 04 33 33 34 33 CS 16',
Check code (CS) is as below.
68 + 01 + 00 + 00 + 00 + 00 + 00 + 68 + 11 + 04 + 33 + 33 + 34 + 33 = 1B3
CS = B3 (CS is lower than 1 byte.)
End symbol (16H)
16H is at the end of the frame.
Command for each control code
Read out data
Data read out by the data identifications.
• Command from master; Control code 11H
68H
A0
A1
Transmission address
• Response from the Slave (normal)
68H
A0
A1
Transmission address
DI0
continue
(Add 33H to data identification value)
1435710000/01/05.13
A2
A3
A4
(A0 to A5 or AAH)
continue
A2
A3
A4
(A0 to A5)
DI1
DI2
Data identification
A5
68H
11H
Control code
DI0
DI1
DI2
Data identification
(Add 33H to data identification value)
A5
68H
91H
(Data identification byte +
DI3
N1
Data (Add 33H to measuring
value and setting value)
04H
Data length
DI3
CS
L
Data length
data byte)
•••
Nm
CS
continue
16H
continue
16H