Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Settings

7.
Settings
You can set parameters for measuring and other functions using the keys on Power Monitor.
After wiring Power Monitor and CT, power on and set the parameter for power measurement, Power Monitor
can measure the electric power. In order to use the other functions, set other parameters as required.
Key functions in setting mode
<MODE>
<SET>
<SHIFT/∇>, <ITEM/∆>
Parameters for power measurement
Item
Phase/Wire system
CT type
Primary side current of CT
VT ratio
Conversion rate (P)
Conversion rate (-P)
Parameters for communication
Item
Protocol
Device number
Transmission speed
Transmission format
Stop bit
Response time
24
Change to setting mode
Set the items and values
Select items and change values
Range
1P2W, 1P3W, 3P3W, 3P4W
1, 5 [A]
1 to 4000 [A]
1.00 to 600.00
0.00 to 99.99/1kWh
0.00 to 99.99/1kWh
Range
MEWTOCOL, MODBUS(RTU), DL/T645-2007
MEWTOCOL
1 to 99
MODBUS(RTU)
1 to 247
DL/T645-2007
0 to 9999
38400, 19200, 9600,4800, 2400, 1200 [bps]
8b-o(8bit odd), 8b-n(8bit none),8bit-E(8bit even)
1,2
1 to 99 [ms]
Initial value
1P2W
5A
5A
1.00
10.00
10.00
Initial value
MEWTOCOL
1
19200
8b-o
1
5
1435710000/01/05.13