Herunterladen Inhalt Inhalt Diese Seite drucken

Weidmuller Power Monitor Handbuch Seite 228

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Communications
Data identification
DI
DI
DI
DI
3
2
1
0
01
Voltage 1
02
Voltage 2
02
01
00
03
Voltage 3
FF
Voltage data block
01
Line voltage 1-2
02
Line voltage 2-3
02
0C
00
03
Line voltage 3-1
FF
Line voltage data block
01
Current 1
02
Current 2
02
02
00
03
Current 3
FF
Current data block
00
Power factor (average)
01
Power factor 1
02
06
02
00
Power factor 2
03
Power factor 3
FF
Power factor data block
02
Frequency (average)
02
80
00
07
Temperature
*
For signed data, the upper bit shows the sign. '0' shows plus and '1' shows minus.
106
Name
Data format
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.XXX
XXX.XXX
XXX.XXX
X.XXX
X.XXX
X.XXX
X.XXX
XX.XX
Unit
Byte
V
2
V
2
V
2
6
V
2
V
2
V
2
6
A
3
A
3
A
3
9
2
2
2
2
8
Hz
2
XX.X
2
Range
0 to 999.9
0 to 999.9
0 to 999.9
0 to 999.9
0 to 999.9
0 to 999.9
0 to 999.999
0 to 999.999
0 to 999.999
-1.000 to 1.000
-1.000 to 1.000
-1.000 to 1.000
-1.000 to 1.000
0 to 99.99
-99.9 to 99.9
1435710000/01/05.13
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis