Wiring
How to connect the CT
(1) Power off the measured devices.
(2) Install the appropriate CT.
(3) Remove terminal block of Power Monitor.
(4) Connect the CT to the terminal block.
(5) Insert the terminal stand securely.
(6) After ensuring that all the wiring is correct, turn on the power of the load and Power Monitor.
(Connection example)
How to set the parameters for the CT
(1) Select CT type (CT-T) in accordance with the CT to be used.
(Select '5A' if secondary side current of the CT used is 5 A. Select '1A' if secondary side current of the
CT used is 1 A.)
(2) Set the primary current of the measured CT at primary side current of CT setting mode (CT-1).
<ex> If the measured CT is 400 A / 1 A or 400 A / 5 A, set to '400'.
(3) Connect the CT according to the CT direction, power side (K) to load side (L).
1435710000/01/05.13
* Connect CT wiring and terminal block
securely, otherwise it will cause a CT
breakdown.
* Never remove the terminal block when
current is applied to the load. It will cause
electric shock or the CT breakdown.
21